S26C
FOR ONE OR TWO 2-PIN COMPACT LAMPS
APPLICATION
OPERATION
When AC power fails, the emergency ballast automatically starts and operates the lamp at full power the first few seconds to eliminate the need for a ground plane, then reduces to a lower lumen output to conserve battery power. The lamp operates in the emergency mode for a minimum of 90 minutes. When AC power is restored, the emergency ballast automatically returns to the charging mode.
INSTALLATION
This equipment does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched lead must be connected to the emergency ballast. If used in an emergency-only fixture, no AC ballast is necessary. Installation is not recommended in fixtures where the ambient temperature may fall below 0°C for extended periods. It is also not suitable for installation in heated air outlet fixtures, and wet, damp, or hazardous location fixtures. For simple visual inspection of the charging indicator light and easy operational testing, the test/monitor plate can be installed near the fixture wall switch. Or, it can be installed in the ceiling near the fixture to ensure an unobtrusive installation. S26C has two wire harness with 2' of flexible conduit, one at each end of the ballast.
UL and CODE COMPLIANCE
This emergency ballast has been tested and approved by Underwriters Laboratories in accordance with the standards set forth in UL924 - "Emergency Lighting and Power Equipment," and is UL LISTED. Emergency illumination exceeds the National Electrical Code (NEC), Life Safety Code (NFPA-LSC) and UL 90-minute requirements.
BATTERY
The S26C contains a high-temperature nickel cadmium battery. These batteries are maintenance-free, can be safely installed inside the ballast channel, and have a life expectancy of 7 to 10 years.
EMERGENCY ILLUMINATION
This equipment produces 450 - 950 lumens initial emergency illumination, depending on wattage of lamp used, for a minimum of 90 minutes.
SPECIFICATION
WARRANTY
Model S26C is warranted for two (2) full years from date of purchase. This warranty covers only properly installed
SIDE-LITE emergency ballasts used under normal conditions. For the warranty period SIDE-LITE will, at its option, repair or replace without charge a defective emergency ballast, provided it is returned transportation prepaid, and our inspection determines it to be defective under terms of the warranty. Repair or replacement, as stated above, shall constitute the purchaser's exclusive warranty, which does not extend to transportation, installation, labor or any other charges; nor does it apply to any equipment of another manufacturer used in conjunction with the emergency ballast.
| Product Summary | ||
| UL Listed | Factory or Field Installation | |
| Initial Light Output | 450 - 950 Lumens | |
| Illumination Time | 90 Minutes | |
| Test Switch | Single Pole |
|
| Charging Indicator Light | LED | |
| Recharge Time | 24 Hours | |
| Ballast Temperature Rating | 00 to + 550C | |
| Dual Input Voltage | 120/277 VAC, 60 Hz | |
| Input Current | 270 mA | |
| Battery | High Temperature, Maintenance-Free Nickel Cadmium Battery
7 to 10 Year Life Expectancy |
|
| Electrical Rating | 3.5 W | |
| Warranty | 2 Years (NOT pro-rata) | |
| Weight | 3.9 lbs. | |
| Dimensions | 12" x 2.4" x 1.5" (304 mm x 60 mm x 38 mm) 2' of flex conduit each end Mounting center 11.5" (292 mm) |
|