Side-Lite Emergency Ballasts
Products
S60FCW
S60FCW
COLD WEATHER FLOURESCENT EMERGENCY BALLAST
EXTENDED TEMPERATURE RANGE (-20°C TO 55°C)
ONE OR TWO-LAMP EMERGENCY ILLUMINATION

APPLICATION
TABLE 1
Lamp Diameter
Base Type
Power
Length
# of Lamps
Emergency
T8, T9, T10, T12
(1", 1-1/4", 1-1/2")
SIngle Or Bipin
17- 40 W (2'- 4')
1
2
40 - 215 W (5'-8')
1
The S60FCW fluorescent emergency ballast works in conjunction with an AC ballast to convert new or existing fluorescent fixtures into emergency lighting. The emergency ballast consists of a high-temperature nickel-cadmium battery, charger and electronic circuitry in one compact black case. The S60FCW can be used with most 17 - 215 W (2'-8') T8, T9, T10 or T12 fluorescent lamps without integral starters, including U-shaped, HO, VHO, circline and energy-saving. One- or two-lamp operation may be selected (see Table 1). It is also compatible with most one-, two-, three- and four-lamp electronic, standard, energy-saving and dimming AC ballasts. If used in an emergency-only fixture, no AC ballast is necessary. The S60FCW is suitable for indoor and damp locations and for sealed & gasketed fixtures. It is not suituble for air handling heated air outlets or for wet or hazardous locations. For information about specific lamp and ballast compatibility, please call the factory.

OPERATION
When AC power fails, the S60FCW immediately switches to the emergency mode, operating either one or two lamps at a reduced lumen output for a minimum of 90 minutes. When AC power is restored, the S60FCW either heats the battery or charges it, depending on the temperature.

INSTALLATION
The S60FCW does not affect normal fixture operation and may be used with either a switched or unswitched fixture. If a switched fixture is used, an unswitched hot lead must be connected to the emergency ballast. The emergency ballast must be fed from the same branch circuit as the AC ballast. The S60FCW may be installed inside the fixture. Contact the manufacturer for installation on top of or remote from the fixture.

UL and CODE COMPLIANCE
The S60FCW has been tested by Underwriters Laboratories in accordance with the standards set forth in UL 924, "Emergency Lighting and Power Equipment," and is UL Listed for factory or field installation. Emergency illumination time exceeds the National Electrical Code (NEC), Life Safety Code(NFPA-LSC) and UL 90-minute requirements.

BATTERY
In order to handle the extended temperature range of its intended applications, the S60FCW uses a specially constructed, high-temperature nickel-cadmium battery. This battery requires no maintenance and has a life expectancy of 7 to 10 years.

EMERGENCY ILLUMINATION
Depending upon the number (one or two), wattage and type of lamps selected, the S60FCW produces up to 1500 lumens initial emergency light output (see Table 2) at 25° C. For lumens at different tempertures for one or two 32 W 4´ T8 lamps, see Table 3. If two-lamp operation is selected, light output is evenly divided between the lamps for better distribution of emergency illumination.

SPECIFICATION
Table 2
Lamp
Lumens
1 Lamp
2 Lamps
FO32, FBO31 T8
1500
1500
FO96 T8
1500
 
F96T8/HO
1425
 
F96 T12, HO, VHO
1300
 
FO25, FBO24 T8
1350
1425
FO17, FB016 T8
1250
1150
F4OT12, F4OU
1300
1300
F48T12/HO
1400
 
Partial Listing of Lamps operated
* indicates light output lower than 1100 lumens
Emergency lighting shall be provided by using a standard fluorescent fixture equipped with a Side-Lite S60FCW emergency ballast. The S60FCW shall have temperature-control circuitry to fulfill both low-temperature and high-temperature operation. This emergency ballast shall consist of a high-temperature, maintenance-free nickel-cadmium battery, charger and electronic circuitry contained in one 13 3/8" x 2 3/8" x 1 1/2" black metal case. A solid-state charging indicator light to monitor the charger and battery, a single-pole test switch and installation hardware shall be provided. The emergency ballast shall be capable of operating [one or two] _________ fluorescent lamp(s) (see Table 1) at _________lumens (see Table 2) initial light output in the emergency mode for a minimum of 90 minutes. It is suitable for use in damp locations and sealed & gasketed fixtures. The storage and operating temperture range for the S60FCW shall be -20°C to +55°C. The S60FCW shall have 16 Watts of input power and a 25.2 Watt-hour battery capacity and shall exceed emergency standards set forth by the current NEC. The emergency ballast shall be UL Listed for installation inside, on top of or remote from the fixture and shall be warranted for a full five years from date of purchase. Contact the manufacturer for installation on top of or remote from the fixture.

WARRANTY
Model S60FCW is warranted for five (5) full years from date of purchase. This warranty covers only properly installed Side-Lite emergency ballasts used under normal Conditions. For the warranty period, Side-Lite will, at its option, repair or replace without charge a defective emergency ballast, provided it is returned to the factory transportation prepaid and our inspection determines it to be defective under terms of the warranty. Repair or replacement, as stated above, shall constitute the purchaser s exclusive warranty, which does not extend to transportation, installation, labor or any other charges; nor does it apply to any equipment of another manufacturer used in conjunction with the emergency ballast.
 
Product Summary
UL Listed Factory or Field Installation
Initial Light Output 1100 - 1400 Lumens
Illumination Time 90 Minutes
Test Switch Single Pole
Charging Indicator Light LED
Recharge Time 24 Hours
Ballast Temperature Rating -200C to + 550C (-40F to + 1310F)
Dual Input Voltage 120/277 VAC, 60 Hz
Input Current 270 mA
Battery Charging Current 320 mA
Battery High Temperature, Maintenance-Free Nickel Cadmium Battery
7 to 10 Year Life Expectancy
Warranty 5 Years (NOT pro-rata)
Weight 3.2 lbs.
Audible Alarm User-Selectable
Dimensions 13.3" x 2.4" x 1.5" (339 mm x 60 mm x 38 mm)
Mounting center 12.8" (325 mm)

2008 © Side-Lite™ All rights reserved
P.O. Box 793 • Olive Branch, MS 38654
TOLL-FREE 888-900-7544 • Customer Service 800-480-4848 • FAX 662-349-0769